Acrel ADL400 Three-Phase Din Rail Energy Meter
ADL400 din-rail multifunctional energy meter is an intelligent instrument designed mainly for electric energy statistics and management needs of power systems, industrial and mining enterprises, and public facilities. The product has the advantages of high precision, small size, and convenient installation. It can integrate power parameter measurement and power metering and assessment management, and provide various power data statistics for the last 48 months. It has 2~31 sub-harmonic and total harmonic content detection. With RS485 communication interface, MODBUS-RTU or DL/T645 protocol can be selected. The energy meter can be widely used in various control systems, SCADA systems and energy management systems.
Specification | Details |
---|---|
Measurement | |
Voltage | |
Reference Voltage | 3×100V / 3×380Vac, 3×57.7/100Vac, 3×220/380Vac (Can normally work under 1.2 times of rated voltage) |
Consumption | <10VA (Single phase) |
Impedance | >2MΩ |
Accuracy Class | Error ±0.2% |
Current | |
Input Current | 3×1(6)A, 3×10(80)A |
Consumption | <1VA (Single phase rated current) |
Accuracy Class | Error ±0.2% |
Power | Active, reactive, apparent power, Error ±0.5% |
Frequency | 45~65Hz, Error ±0.2% |
Metering | |
Energy | Active energy (Accuracy class: 0.5), Reactive energy (Accuracy class: 2) |
Clock | ≤0.5s/d |
Digital Signal | |
Energy Pulse Output | 1 active photocoupler output |
Pulse | |
Width of Pulse | 80 ±20ms |
Pulse Constant | 400imp/kWh, 10000imp/kWh (Corresponds with the basic current) |
Communication | |
Interface & Protocol | RS485: Modbus RTU |
Communication Address Range | Modbus RTU: 1 ~ 247 |
Baud Rate | 1200bps ~ 19200bps |
Environment | |
Working Temperature | -25℃ ~ +55℃ |
Relative Humidity | ≤95% (No condensation) |
Features of ADL400 Three-Phase Din Rail Energy Meter
It can measure all electric power parameters including voltage U, current I, active power P, reactive power Q, apparent power S, power factor PF, frequency, 31st harmonic and total harmonic content;
It can measure the current combined active energy, forward active energy, reverse active energy, forward reactive energy, and reverse reactive energy;
It can count the historical electric energy of the last 48 months (electric energy of each rate) and the historical electric energy of the last 90 days (electric energy of each rate).