Delta DVP48EC00T3 PLC EC3 (Original)
- Motor Type: Stepper Motor
- Origin: CN(Origin)
- Model Number: DVP48EC00T3
Electrical Specifications
Model Item |
10EC 00_3 |
14EC 00_3 |
16EC 00_3 |
20EC 00_3 |
24EC 00_3 |
30EC 00_3 |
32EC 00_3 |
40EC 00_3 |
48EC 00_3 |
60EC 00_3 |
||
Power supply voltage |
100 ~ 240VAC (-15% ~ 10%), 50/60Hz + – 5% |
|||||||||||
Operation |
DVP-EC3 starts to run when the power supply rises to 95 ~ 100V AC and stops when the power supply drops to 70V AC. It continues to run for 10ms after the power supply is cut off. |
|||||||||||
Power supply fuse |
2A/250VAC |
|||||||||||
Power consumption |
12VA |
15.6VA |
22.5VA |
|||||||||
DC24V current output |
200mA |
300mA |
400mA |
|||||||||
Power supply |
DC24V output short circuit |
|||||||||||
Voltage withstand |
1,500VAC (Primary-secondary), 1,500VAC (Primary-PE), 500VAC (Secondary-PE) |
|||||||||||
Insulation resistance |
> 5MΩ at 500VDC (between all I/O points and earth) |
|||||||||||
Noise immunity |
ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV, Analog & Communication I/O: 1kV RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m |
|||||||||||
Grounding |
The diameter of grounding wire shall not be less than that of L, N terminal of the power supply. (When many PLCs are in use at the same time, please make sure every PLC is properly grounded.) |
|||||||||||
Operation/storage |
Operation: 0 °C ~55 °C (temperature), 50~95% (humidity), pollution degree 2 Storage: -25 °C ~70 °C (temperature), 5~95% (humidity) |
|||||||||||
Agency approvals |
UL508 European community EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC |
|||||||||||
Vibration/shock immunity |
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea) |
|||||||||||
RS-485 Port |
No |
Yes |
||||||||||
Weight (g) |
R |
205 |
210 |
220 |
310 |
322 |
325 |
340 |
380 |
540 |
560 |
|
T |
192 |
195 |
198 |
285 |
288 |
290 |
295 |
340 |
505 |
510 |
There are no reviews yet.