I/O expansion unit FX2N-32ER-ES/UL
- Manufacturer : Mitsubishi Electric
- FX2N-32ER-ES/UL
- I / O expansion unit FX2N – 32ER – ES / UL
- Application sequencer : FX1N, FX3G, FX2N, FX3U
- mass : 0.65 Kg
- Rated voltage : AC 100 V to 240 V
- Voltage tolerance range : AC 85V ~ 264V
- Rated frequency : 50/60 Hz
- Power supply fuse : 250 V 3.15 A (3A)
- Inrush current : AC 100 V: maximum 40 A 5 ms or less AC 200 V: maximum 60 A 5 ms or less
- power consumption : 30 W
- 24 VDC service power supply : 24 VDC 250 mA or less When input / output expansion block is connected, 24 VDC service power is consumed.
- Input specification :
- Number of input points : 16 points
- Input connection shape : Removable terminal block (M3 screw)
- Input format : Sink / source
- Input signal voltage : DC 24 V ± 10%
- Input impedance : 4.3 kΩ
- Input signal current : 5 mA / 24 VDC
- Input ON sensitivity current : 3.5 mA or more
- Input OFF sensitivity current : 1.5 mA or less
- Input response time : About 10 ms
- Input signal format : Sink: no-voltage contact input or NPN open collector transistor source: no-voltage contact input or PNP open collector transistor
- Input circuit insulation : Photocoupler insulation
- Input operation display : LED on the panel when input is ON
- Number of output points : 16 points
- Output connection shape : Removable terminal block (M3 screw)
- Output type / format : relay
- External power supply : DC 30 V or less AC 240 V or less (When not compliant with CE, UL, cUL standard, AC 250 V or less)
- Maximum load Resistive load : Please set the total load current per 2A / 1 point common as follows. . Output 4 points / common: 8 A or less
- Inductive load : 80VA
- Minimum load : DC 5 V 2 mA (reference value)
- Response time OFF → ON : About 10 ms
- ON → OFF : About 10 ms
- Circuit insulation : Mechanical insulation
- Output operation indication : LED lit when relay coil is energized
- Ambient temperature : 0 to 55 ° C. … Operating -25 to 75 ° C. ….. Save
- Relative humidity : 5 to 95% RH (noncondensing)…. in operation
- Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2
- Frequency: 57 to 150 Hz : Acceleration: 4.9 m / s 2 Ten times in each of X, Y, Z directions (80 minutes in total in total) The criterion is based on IEC 61131-2
- Direct installation Frequency: 10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2
- Frequency: 57 to 150 Hz : Acceleration: 9.8 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2
- Impact resistance : 147 m / s 2 , working time 11 ms, criterion for judgment three times in X, Y, Z directions by sine half-wave pulse is according to IEC 61131-2
- Noise immunity : Noise voltage with 1,000 Vp-p, noise width 1 μs, rising 1 ns, with noise si
- tor with period of 30 to 100 Hz
- Withstand voltage : Between the power supply terminal (AC power supply) and the earth terminal: AC 1500 V for 1 minute 24 VDC Service power supply and between the input terminal (24 VDC) and the earth terminal: 500 V AC for 1 minute Between the output terminal (relay)
- Insulation resistance : Between each terminal and earth terminal: 500 MV DC 500 MΩ or more with an insulation resistance meter
- ground : Class D grounding (grounding resistance: 100 Ω or less)Grounding should be dedicated ground or common ground.
- Use atmosphere : There is no corrosive property, flammable gas, conductive dust (dust) is not serious
- Use altitude : Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.
- Shipping Weight : 1.7 Kg